DRC-100B

PDFPrintEmail

  • Universal AC input / Full range

  • Protections: Short circuit / Overload / Over voltage

  • Battery low / Battery reverse polarity protection protection by fuse

  • Can be installed on DIN rail TS-35/7.5 or 15

  • Alarm signal for AC OK and Battery low (via relay)

  • Cooling by free air convection

  • LED indicator for power on

  • 100% full load burn-in test

  • 3 years warranty

DRC-100B
Sales price without tax 65,90 €
Price / kg:
Description
SPECIFICATION
MODEL DRC-100B
OUTPUT OUTPUT NUMBER CH1 CH2
DC VOLTAGE 27.6V  27.6V
RATED CURRENT 2.25A  1.25A
CURRENT RANGE 0 ~ 3.5A --------
RATED POWER 96.6W
RIPPLE & NOISE (max.) Note.2 240mVp-p --------
VOLTAGE ADJ. RANGE CH1:24 ~ 30V
VOLTAGE TOLERANCE Note.3 ±1.0% --------
LINE REGULATION ±0.5% --------
LOAD REGULATION ±0.5% --------
SETUP, RISE TIME Note.4

2400ms, 50ms/230VAC

2400ms, 50ms/115VAC at full load

HOLD UP TIME (Typ.)

50ms/230VAC

10ms/115VAC at full load

INPUT VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 89%
AC CURRENT (Typ.)

1.8A/115VAC

1.1A/230VAC

INRUSH CURRENT (Typ.)

COLD START 30A/115VAC

60A/230VAC

PROTECTION OVERLOAD 105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER VOLTAGE CH1:28.98 ~ 37.26V
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF 20±1V
FUNCTION AC OK Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30V/1A
BATTERY LOW Relay contact output, OFF : Battery OK ; ON : Battery Low ; max. rating : 30V/1A
Battery low voltage : < 22V
ENVIRONMENT WORKING TEMP. -30 ~ +70°C (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85°C, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/°C (0 ~ 50°C) on CH1 output
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY &EMC(Note 5 SAFETY STANDARDS UL60950-1, TUV EN60950-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH
EMC EMISSION Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A, EAC TP TC 020 ; meet EN54-4 for fire detection and fire alarm systems
OTHERS MTBF 410.1K hrs min. MIL-HDBK-217F (25°C)
DIMENSION 55*90*100mm (W*H*D)
PACKING 0.37Kg; 30pcs/12.1Kg/0.82CUFT
NOTE

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.

5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)

6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.

7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher °C°Cthan 2000m(6500ft).

 

DRC-100B Specification