MDR-40-24

PDFPrintEmail

  • Universal AC input/Full range

  • Protections: Short circuit / Overload / Over voltage

  • Cooling by free air convection

  • Can be installed on DIN rail TS-35/7.5 or 15

  • Class I, Div 2 Hazardous Locations T4

  • LED indicator for power on

  • DC OK relay contact

  • No load power consumption<0.75W

  • 100% full load burn-in test

  • 3 years warranty

MDR-40-24
Sales price without tax 24,50 €
Τιμή / kg:
Description
SPECIFICATION
MODEL MDR-40-24
OUTPUT DC VOLTAGE 24V
RATED CURRENT 1.7A
CURRENT RANGE 0 ~ 1.7A
RATED POWER 40.8W
RIPPLE & NOISE (max.) Note.2 150mVp-p
VOLTAGE ADJ. RANGE 24 ~ 30V
VOLTAGE TOLERANCE Note.3 ±1.0%
LINE REGULATION ±1.0%
LOAD REGULATION ±1.0%
SETUP, RISE TIME Note.5

500ms, 30ms/230VAC

500ms, 30ms/115VAC at full load

HOLD UP TIME (Typ.)

50ms/230VAC

20ms/115VAC at full load

INPUT VOLTAGE RANGE

85 ~ 264VAC

120 ~ 370VDC

FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 88%
AC CURRENT (Typ.)

1.1A/115VAC

0.7A/230VAC

INRUSH CURRENT (Typ.)

COLD START 30A/115VAC

60A/230VAC

LEAKAGE CURRENT <1mA / 240VAC
PROTECTION OVERLOAD 105 ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE 31.2 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
FUNCTION DC OK ACTIVE SIGNAL (max.) Relay contact rating(max.): 30V/1A resistive
ENVIRONMENT WORKING TEMP. -20 ~ +70°C (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85°C, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/°C (0 ~ 50°C)
VIBRATION Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
SAFETY &EMC (Note 4) SAFETY STANDARDS UL508, UL62368-1, TUV EN62368-1,,Class I, Div. 2 Group A, B, C, D Hazardous Locations T4,EAC TP TC 004BSMI CNS14336-1, AS/NZS 60950.1 approved
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH
EMC EMISSION Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B
EMC IMMUNITY Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A, EAC TP TC 020
OTHERS MTBF 301.7K hrs min. MIL-HDBK-217F (25°C)
DIMENSION 40*90*100mm (W*H*D)
PACKING 0.3Kg; 42pcs/13.6Kg/0.82CUFT
NOTE

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to "EMI testing of component power supplies." (as available on http://www.meanwell.com)

5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.

6. The ambient temperature derating of 3.5°C /1000m with fanless models and of 5°C /1000m with fan models for operating altitude higher than 2000m(6500ft).

Product Liability Disclaimer For detailed information, please refer tohttps://www.meanwell.com/serviceDisclaimer.aspx

 

MDR-40-24 Specification